Commissioning
5.5 Quick commissioning
SINAMICS V20 Inverter
54
Operating Instructions, 07/2012, A5E03728167
Parameter
Description
Factory
default
Default for
AP020
Remarks
P1080[0]
Minimum frequency
0
20
Inverter running at a lower speed
inhibited
P1120[0]
Ramp-up time
10
10
Ramp-up time from zero to
maximum frequency
P1121[0]
Ramp-down time
10
20
Ramp-down time from maximum
frequency to zero
Application macro AP021 - Compressor applications
Parameter
Description
Factory
default
Default for
AP021
Remarks
P1300[0]
Control mode
0
0
Linear V/f
P1080[0]
Minimum frequency
0
10
Inverter running at a lower speed
inhibited
P1312[0]
Starting boost
0
30
Boost only effective when
accelerating for the first time
(standstill)
P1311[0]
Acceleration boost
0
0
Boost only effective when
accelerating or braking
P1310[0]
Continuous boost
50
50
Additional boost over the complete
frequency range
P1120[0]
Ramp-up time
10
10
Ramp-up time from zero to
maximum frequency
P1121[0]
Ramp-down time
10
10
Ramp-down time from maximum
frequency to zero
Application macro AP030 - Conveyor applications
Parameter
Description
Factory
default
Default for
AP030
Remarks
P1300[0]
Control mode
0
1
V/f with FCC
P1312[0]
Starting boost
0
30
Boost only effective when
accelerating for the first time
(standstill)
P1120[0]
Ramp-up time
10
5
Ramp-up time from zero to
maximum frequency
P1121[0]
Ramp-down time
10
5
Ramp-down time from maximum
frequency to zero
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...