Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
162
Operating Instructions, 07/2012, A5E03728167
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P1032
Inhibit reverse direction
of MOP
0 - 1
1
T
-
-
U16
2
Inhibits reverse setpoint selection of the MOP.
0
Reverse direction is allowed
1
Reverse direction inhibited
Note:
Setting 0 enables a change of motor direction using the motor potentiometer setpoint (increase / decrease
frequency).
If P1032 = 1 and P1000 = 1 or 1X, then reverse motor direction will be inhibited.
P1035[0...2] BI: Enable MOP (UP-
command)
-
19.13
T
-
CDS
U32 /
Bin
3
Defines source for motor potentiometer setpoint increase frequency.
Notice:
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.1
Hz. When the signal is enabled longer than 1 second the ramp generator accelerates with the rate of
P1047.
P1036[0...2] BI: Enable MOP
(DOWN-command)
-
19.14
T
-
CDS
U32 /
Bin
3
Defines source for motor potentiometer setpoint decrease frequency.
Notice:
If this command is enabled by short pulses of less than 1 second, the frequency is changed in steps of 0.1
Hz. When the signal is enabled longer than 1 second the ramp generator decelerates with the rate of
P1048.
P1040[0...2] Setpoint of the MOP [Hz] -599.00 -
599.00
5.00
U, T
-
DDS
Float 2
Determines setpoint for motor potentiometer control (P1000 = 1).
Dependency: Motor potentiometer (P1040) must be chosen as main setpoint or additional setpoint (using P1000).
Note:
If motor potentiometer setpoint is selected either as main setpoint or additional setpoint, the reverse
direction will be inhibited by default of P1032 (inhibit reverse direction of MOP). To re-enable reverse
direction, set P1032 = 0.
A short press of the 'up' or 'down' keys (e.g.: operator panel) will change the frequency setpoint in steps of
0.1 Hz. A longer press will cause an accelerated frequency setpoint change.
The start value gets active (for the MOP output) only at the start of the MOP. P1031 influences the start
value behavior as follows:
•
P1031 = 0:
P1040 gets immediately active in the OFF-state and when changed in the ON-state, it gets active after
the next OFF and ON cycle.
•
P1031 = 1:
The last MOP output before stop is stored as starting value, since storing is selected, so a change of
P1040 while in ON-state has no effect. In OFF-state P1040 can be changed.
•
P1031 = 2:
The MOP is active every time, so the change of P1040 affects after the next power cycle or a change
of P1031 to 0.
P1041[0...2] BI: MOP select setpoint
automatically / manually
-
0
T
-
CDS
U32 /
Bin
3
Sets the signal source to change over from manual to automatic mode. If using the motorized
potentiometer in the manual mode the setpoint is changed using two signals for up and down e.g. P1035
and P1036. If using the automatic mode the setpoint must be interconnected via the connector input
(P1042).
0: manually
1: automatically
Notice:
Refer to: P1035, P1036, P1042
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...