Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
131
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
[1]
Not used
[2]
Rated high overload (HO) current
Note:
The rated high overload (HO) current r0207[2] values correspond to suitable 4-pole Siemens standard
motors (IEC) for the selected load cycle (see diagram). r0207[2] is the default value of P0305 in
association with the HO application (load cycle).
,QYHUWHUFXUUHQWSRZHU
5DWHGLQYHUWHUFXUUHQWFRQWLQXRXV
%DVHORDGFXUUHQWZLWKRYHUORDGFDSDELOLW\
6KRUWWLPHFXUUHQW
U
U>@
V
V
W
r0208
Rated inverter voltage
[V]
-
-
-
-
-
U32
2
Displays nominal AC supply voltage of inverter.
Note:
r0208 = 230: 200 - 240 V + / - 10 %
r0208 = 400: 380 - 480 V + / - 10 %
r0208 = 575: 500 - 600 V + / - 10 %
r0209
Maximum inverter
current [A]
-
-
-
-
-
Float 2
Displays maximum output current of inverter.
Dependency: r0209 depends on the derating which is affected by pulse frequency P1800, ambient temperature and
altitude. The data of deration is given in the Operating Instructions.
P0210
Supply voltage [V]
0 - 1000
400
T
-
-
U16
3
P0210 defines the supply voltage. Its default value depends upon the type of inverter. If P0210 does not
correspond to the supply voltage, then it must be modified.
Dependency: Optimizes Vdc controller, which extends the ramp-down time if regenerative energy from motor would
otherwise cause DC-link overvoltage trips.
Reducing the value enables controller to cut in earlier and reduce the risk of overvoltage.
Set P1254 ("Auto detect Vdc switch-on levels") = 0. Cut-in levels for Vdc controller and compound braking
are then derived directly from P0210 (supply voltage):
•
Vdc_min switch-on level (r1246) = P1245 * sqrt(2) * P0210
•
Vdc_max switch-on level (r1242) = 1.15 * sqrt(2) * P0210
•
Dynamic braking switch-on level = 1.13 * sqrt(2) * P0210
•
Compound braking switch-on level = 1.13 * sqrt(2) * P0210
Set P1254 ("Auto detect Vdc switch-on levels") = 1. Cut-in levels for Vdc controller and compound braking
are then derived from r0070 (DC-link voltage):
•
Vdc_min switch-on level (r1246) = P1245 * r0070
•
Vdc_max switch-on level (r1242) = 1.15 * r0070
•
Dynamic braking switch-on level = 0.98 * r1242
•
Compound braking switch-on level = 0.98 * r1242
Auto-detection calculations are only performed when the inverter has been in standby for over 20s. When
pulses are enabled, the calculated values are frozen until 20s after pulses cease.
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...