Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
207
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
•
P2350 = 4
This tuning only changes values of P and I and should be a quarter damped response.
The option to be selected depends on the application but broadly speaking option 1 will give a good
response, whereas if a faster response is desired option 2 should be selected.
If no overshoot is desired then option 3 is the choice. For cases where no D term is wanted then option 4
can be selected.
The tuning procedure is the same for all options. It is just the calculation of P and D values that is different.
After autotune this parameter is set to zero (autotune completed).
P2354
PID tuning timeout
length [s]
60 - 65000 240
U, T
-
-
U16
3
This parameter determines the time that the autotuning code will wait before aborting a tuning run if no
oscillation has been obtained.
P2355
PID tuning offset [%]
0.00 -
20.00
5.00
U, T
-
-
Float 3
Sets applied offset and deviation for PID autotuning.
Note:
This can be varied depending on plant conditions e.g. a very long system time constant might require a
larger value.
P2360[0...2] Enable cavitation
protection
0 - 2
0
U, T
-
DDS
U16
2
Cavitation protection enabled.
Will generate a fault / warning when cavitation conditions are deemed to be present.
7
U
ಹ
!
)HHGEDFNIORZ
SUHVVXUHVHQVRU
7ULSOHYHO
3,'6FDOHGIHHGEDFN
>@
6WDWXVZRUGELW3,'PLQLPXPOLPLWUHDFKHG
6WDWXVZRUGELW3,'PD[LPXPOLPLW
UHDFKHG
6WDWXVZRUGELW3,'LQYHUWHUUXQQLQJ
&DYLWDWLRQSURWHFWLRQHQDEOH
&DYLWDWLRQSURWHFWLRQGLVDEOHG
7ULJJHUFDYLWDWLRQZDUQLQJ$
7ULJJHUFDYLWDWLRQIDXOW)
1RWXVHG
Cavitation Protection Logic Diagram
&DYLWDWLRQSURWHFWLRQGHOD\
3,'HQDEOHGLVDEOH
&DYLWDWLRQ7KUHVKKROG
ಹ>@
3
3
3
5
5
5
3&'6
>V@
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...