Commissioning
5.6 Function commissioning
SINAMICS V20 Inverter
92
Operating Instructions, 07/2012, A5E03728167
5.6.3.7
Setting the flying start function
Functionality
The flying start function (enabled using P1200) allows the inverter to be switched onto a
motor which is still spinning by rapidly changing the output frequency of the inverter until the
actual motor speed has been found. Then, the motor runs up to setpoint using the normal
ramp time.
Flying start must be used in cases where the motor may still be turning (e.g. after a short
mains break) or can be driven by the load. Otherwise, overcurrent trips will occur.
W
I
IBVHDUFKPD[
6HWSRLQWIUHTXHQF\
5DPSXS
0DJQHWL]LQJWLPH
'HPDJQHWL]LQJ
WLPH
)O\LQJVWDUW
3
3
3
3
Setting parameters
Parameter
Function
Setting
P1200
Flying start
Settings 1 to 3 search in both directions:
= 0: Flying start disabled
= 1: Flying start always active
= 2: Flying start active after power on, fault, OFF2
= 3: Flying start active after fault, OFF2
Settings 4 to 6 search only in the direction of the setpoint:
= 4: Flying start always active
= 5: Flying start active after power on, fault, OFF2
= 6: Flying start active after fault, OFF2
P1202[0...2]
Motor-current: flying start [%]
This parameter defines search current used for flying start.
Range: 10 ... 200 (factory default: 100)
Note: Search current settings in P1202 that are below 30%
(and sometimes other settings in P1202 and P1203) may
cause motor speed to be found prematurely or too late, which
can result in F1 or F2 trips.
P1203[0...2]
Search rate: flying start [%]
This parameter sets factor (in V/f mode only) by which the
output frequency changes during flying start to synchronize
with turning motor.
Range: 10 ... 500 (factory default: 100)
Note: A higher value produces a flatter gradient and thus a
longer search time. A lower value has the opposite effect.
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...