CS-I User and Maintenance, R.2.8 ENG
Safco Systems Ltd-Via Isonzo 17/b-20090 Cesano Boscone-Milan-Italy
tel. +39 024504433 Fax +39 024504321 E-mail:[email protected] Web site: www.safcosys.it
87 of 109
7.
Wait, Parameters Loading
The message is displayed for a short period,
initializing parameters, in case it is confirmed
that the default setting of the EEPROM.
Warning YES
8.
ERROR! Phase failure
Lack of at least one of the input phases to the
CS-I / P Check switches, fuses and line
tightness of power cables, ensure that the
voltage level seen by the inverter complies
with the specifications.
WARNING: Perform the checks only after
switching off the system!
Alarm YES
9.
ERROR! VBus Pre-Charge Time out
The dc bus voltage value has not reached
regime in the maximum time expected.
Check switches, fuses and line tightness of
power cables, ensure that the voltage level seen
by the inverter complies with the specifications.
Monitor the absence of voltage anomalies in the
ignition phase.
WARNING: Perform the checks only after
switching off the system! Monitoring should be
carried out by qualified personnel with
appropriate equipment.
Alarm YES
10.
ERROR! VBus out of static range
The dc bus voltage has gone out of range while
the system was not delivering power. Check
and if necessary to monitor power supply
voltages.
WARNING: The monitoring should be carried
out by qualified personnel with appropriate
equipment.
Alarm YES
11.
POWER SUPPLY OFF!
CS-I / P off, bus voltage below 370V with
phase failure. If occurs during the operation,
indicates an anomalous behavior of the supply
network.
Alarm YES
12.
ERROR! 24VP I/O
Lack of voltage 24V I / O: connect properly
(possibly with jumpers) section IO (see chapter
"Commissioning").
Alarm YES
13.
ERROR! Outlet short
It 'has detected a short circuit on the lines of
the outputs; eliminate the cause of short circuit
and reset the system.
Alarm YES
14.
ERROR! FAN 2
Failure of the control circuit of the fan 2
(internal cooling), you must contact the
manufacturer for repair.
Alarm YES
15.
ERROR! Control Mode not allowed
ERROR management system software, report
what happened to the manufacturer.
Alarm YES
16.
ERROR! Internal RT CONTROL
Alarm YES
17.
!! EMERGENCY !!
Emergency button pressed (open contact). The
system is placed in security (IO disabled, IGBT
stops, sw control pause) until the button is
pressed.
Alarm YES