CS-I User and Maintenance, R.2.8 ENG
Safco Systems Ltd-Via Isonzo 17/b-20090 Cesano Boscone-Milan-Italy
tel. +39 024504433 Fax +39 024504321 E-mail:[email protected] Web site: www.safcosys.it
49 of 109
Water SV presence
Range
value:
NO,
YES
Default value
YES
It sets the presence of the cooling water solenoid valve, of the fans and their diagnostic.
Caution:
Never deactivate the water valve if installed otherwise the water cannot circulate
and cool the heat sink, anyway thermal protections are active!.
Current source
Range
value:
Int;
Ext;
Bus
Default value
Int
In Seam mode it set the reference source of current, from parameter set, Int, or from
external set 0-10V (Ext). referred to Imax, when this field bus is present, by setting the
"Bus" the current value is read as cyclic data type word from 100 to 999‰ field bus:
Open Electrodes
Range
value:
(NO-CHK-FLT)
Default
value:
FLT
Enables management of welding electrodes open (CHK) and any error signal (FLT) or total
disabling of the management "NO"
PSW Input
Range
value:
NO,
YES
Default value
YES
Allows use, if YES , of input Pressure Switch on the terminal board or when unused place to
NO, avoids having to make a jumper toward the VP +24...
S/NS Input
Range
value:
NO,
YES
Default value
YES
Allows use, if YES , of input Weld / No weld from the outside on the terminal board or when
unused place to NO, avoids having to make a jumper toward the VP +24...
Password
Range
value:
NO,
YES
Default value
NO
It set the password in input at the menus:
System Parameters, Communications, Inputs/Outputs Test,
Machine Calibration
,
Copy Program
.
the password key sequence is:
see the last one sheet (removable) of the manual.