Chapter 7 Installing, Removing, and Replacing
Installing a Stand-Alone 5UControl Module
Scalar i500 User’s Guide
202
Installing a Stand-Alone 5UControl Module
Required tools:
None
Use this procedure to install a 5U library configuration:
1
Prepare the rack to hold modules, if you want to install your library
in a rack. See
Installing the Library in a Rack
on page 284 for
instructions on installing a rack-mount kit.
2
Make sure all tape drives have been removed from the control
module. See
Adding, Removing, and Replacing Tape Drives
on
page 303 for instructions on removing tape drives.
3
Make sure all power supplies have been removed from the control
module. See
Adding, Removing, and Replacing Power Supplies
on
page 281 for instructions on removing power supplies.
4
Open the library’s I/E station door and access door. Lift the control
module and place it in the desired location.
5
If you are placing the control module in a rack, use the rack ears to
fasten the control module to the rack. For instructions, see
Installing
the Bottom Module in the Rack
on page 293.
6
If not already installed, install the library control blade (LCB) in the
control module. See
Removing and Replacing the Library Control
Blade and LCB Compact Flash Card
on page 276 for instructions on
installing the LCB.
7
Add the tape drives to the module.
8
Install the power supplies. See
Adding, Removing, and Replacing
Power Supplies
on page 281 for instructions on installing power
supplies.
9
Close the library’s I/E station door and access door.
10
Connect all power cords and network data cables. See
Cabling the
Library
on page 172.
11
Install module terminators in the top and bottom module terminator
connectors. See
Cabling the Library
on page 172 for information on
installing the module terminators.
12
Power on the library.
13
Configure the library using the operator panel Setup Wizard.