Chapter 7 Installing, Removing, and Replacing
Cabling the Library
Scalar i500 User’s Guide
172
Taking a Library Offline
7
1
Using the library’s operator panel, select
Operations > Change
Partition Mode
; or, using the web client, select
Operations > Partitions
> Change Mode
.
2
For each partition that you want to take offline, click
Offline
.
3
Click
Apply
.
Cabling the Library
Use the cabling procedure appropriate for your drive type.
Connecting Library SCSI
Cables to Hosts
7
Use this procedure, along with
Figure 16
and
Figure 17
, if you are
installing a library that includes SCSI tape drives:
Warning:
All libraries taller than 14U must be installed in a rack
having a main protective earthing (grounding) terminal,
and power must be supplied via an industrial plug and
socket-outlet and/or an appliance coupler complying with
IEC 60309 (or an equivalent national standard) and having
a protective earth (ground) conductor with a cross
sectional area of at least 1.5 mm
2
(14 AWG).
To ensure proper airflow and access space, Allow 60 cm
(24 inches) in the front and back of the library.