![Quantum Scalar i500 Скачать руководство пользователя страница 185](http://html2.mh-extra.com/html/quantum/scalar-i500/scalar-i500_user-manual_3563454185.webp)
Scalar i500 User’s Guide
170
Chapter 7
7
Installing, Removing, and
Replacing
This chapter describes how to add, remove, and replace hardware within
your library. Adding, removing, or replacing library components may
require you to power off the entire library. There are a few components,
however, that you can service without powering off the library, such as
replacing tape drives. Instead, you may only need to take a specific
partition offline, or you may not need to impact the status of the library at
all.
Warning:
All libraries taller than 14U must be installed in a rack
having a main protective earthing (grounding) terminal,
and power must be supplied via an industrial plug and
socket-outlet and/or an appliance coupler complying with
IEC 60309 (or an equivalent national standard) and having
a protective earth (ground) conductor with a cross
sectional area of at least 1.5 mm
2
(14 AWG).
To ensure proper airflow and access space, Allow 60 cm
(24 inches) in the front and back of the library.
Warning:
Under no circumstances should a rack be moved while
loaded with one or more modules.