Remove a Power Supply
FIGURE 17
Power Supplies and Latches
Figure Legend
1
Power Supply 0
2
Power Supply 1
A lighted amber LED on a power supply indicates that a failure was detected. You can also use
the ILOM
show
faulty
command at the
sc>
prompt.
Note -
The fans of a failed power supply may still be spinning when the system is powered on.
The failed power supply is still okay to remove.
2.
Log in to the ILOM service processor as root.
Refer to the ILOM 3.0 documentation for instructions.
3.
At the ILOM prompt (
->
), type the
stop /SYS/PS
n
command.
The
stop
command indicates if it is okay to perform a hot removal of a power supply. This
command does not perform any action, but it provides a warning if the power supply should not
be removed because the other power supply is not providing power to the server.
Replacing Chassis Components
185
Содержание Sun Netra X4270
Страница 1: ...Sun Netra X4270 Server Service Manual Part No E23171 03 September 2015 ...
Страница 2: ......
Страница 10: ...10 Sun Netra X4270 Server September 2015 ...
Страница 12: ...12 Sun Netra X4270 Server September 2015 ...
Страница 36: ...36 Sun Netra X4270 Server September 2015 ...
Страница 72: ...72 Sun Netra X4270 Server September 2015 ...
Страница 100: ...100 Sun Netra X4270 Server September 2015 ...
Страница 224: ...224 Sun Netra X4270 Server September 2015 ...
Страница 230: ...WDT W WDT watchdog timers 230 Sun Netra X4270 Server September 2015 ...
Страница 237: ...Index V video port location 17 pinout 219 visual notification 29 W watchdog timer setting 50 weight of server 80 237 ...
Страница 238: ...238 Sun Netra X4270 Server September 2015 ...