Install a Second CPU
Ensure that the orientation is correct, as damage might result if the CPU pins are not aligned
correctly.
6.
Lower the pressure plate.
Ensure that the pressure plate sits flat around the periphery of the CPU.
7.
Engage the lever by rotating it downward and slipping it under the catch.
8.
Remove the plastic protective cover from heatsink.
Be careful not to disturb or touch the preinstalled thermal interface material.
9.
Orient the heatsink so the two screws line up with the mounting studs.
The heatsink is not symmetrical.
10.
Use an Allen wrench to tighten the screws alternately one half turn until fully
seated.
Replacing Motherboard Assembly Components
167