9.5
Measurement Functions
EC1000SA
9-9
Average value:
Average value of AC+DC (measures DC component)
Full scale:
±
15.00 A
Display resolution:
0.01 A
Measurement accuracy:
±
(|0.5% of rdg| + 0.08 A)
(at 23
±
5°C, output current is 5% to 100% of the maximum
output current)
Peak value:
Minimum current and maximum current are displayed
separately
Full scale:
±
45.0 Apk
Display resolution:
0.1 Apk
Measurement accuracy:
±
(|2% of rdg| + 0.4 Apk)
(reference value, at 23
±
5°C, sine wave of which frequency is 45
Hz to 65 Hz)
Peak value hold:
Maximum value of
|
max current
|
and
|
min current |
Full scale:
45.0 Apk
Display resolution:
0.1 Apk
c) Output power measurement
Effective power
Full scale:
1200 W
Display resolution:
1 W
Measurement accuracy:
at 45 Hz to 65 Hz
±
(2% of rdg + 1 W)
at DC
±
(3% of rdg + 12 W)
(at 23
±
5°C, load with the power factor 0.5 to lower than 1, 50 V
or higher output voltage, output current is 10% to 100% of the
maximum output current)
Apparent power:
Calculated as output voltage RMS value × output current RMS
value
Full scale:
1400 VA
Display resolution:
1 VA
Measurement accuracy:
at 45 Hz to 65 Hz
±
(2% of rdg + 1 VA)
at DC
±
(3% of rdg + 12 VA)
(at 23
±
5°C, 50 V or higher output voltage, output current is
10% to 100% of the maximum output current)
Содержание EC1000SA
Страница 1: ...NF Corporation PROGRAMMABLE AC DC POWER SOURCE EC1000SA Instruction Manual nbn Austria GmbH...
Страница 2: ...DA00036667 003 PROGRAMMABLE AC DC POWER SOURCE EC1000SA Instruction Manual...
Страница 31: ...2 5 Calibration EC1000SA 2 10 2 5 Calibration To calibrate the EC1000SA contact NF Corporation or our agent...
Страница 236: ...6 9 Notes on Remote Control EC1000SA 6 58...
Страница 260: ...8 5 Backup Battery EC1000SA 8 8...
Страница 280: ...9 17 External Dimensions and Weight EC1000SA 9 20...