5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
60
4349322/01 EN
VACUTAP
®
VV
®
3. Temporarily fasten on-load tap-changer to supporting structure. The sup-
porting flange has through holes for this purpose.
Figure 43: Temporary fastening
5.3.2 Connecting the tap winding and on-load tap-changer take-off
lead
NOTICE
Damage to the on-load tap-changer!
Connecting leads which place mechanical strain on the on-load tap-changer
will damage the on-load tap-changer!
► Establish and secure connections with care.
► Do not twist connection contacts.
► Connect connecting leads without warping or deforming.
► If necessary use an expansion loop for connecting leads.
1. Connect tap winding and on-load tap-changer take-off lead in accordance
with the connection diagram included with the delivery.
2. If connection leads have to cross the open surface of the oil compartment/
change-over selector, there must be a clearance of 50 mm between the
connecting leads and the surface of the oil compartment/change-over se-
lector.
The designations of the on-load tap-changer's connection contacts are
shown in the connection diagram. The connection contacts are provided with
vertical through-holes (11 mm diameter for M10 screws, see appendix).
Содержание VACUTAP VV
Страница 1: ...On load tap changer VACUTAP VV Installation and commissioning instructions 4349322 01 EN ...
Страница 112: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 112 4349322 01 EN VACUTAP VV Figure 109 Mounting protective tube ...
Страница 125: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 125 4349322 01 EN VACUTAP VV Figure 125 Angle of deflection α ...
Страница 182: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 182 4349322 01 EN VACUTAP VV 9 Drawings ...
Страница 188: ......
Страница 195: ......
Страница 197: ......