5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
142
4349322/01 EN
VACUTAP
®
VV
®
Permitted axial displacement
Minor axial displacement of the vertical drive shaft with insulator is permitted
as long as it does not exceed 35 mm per 1000 mm square tube length (that
corresponds to 2°).
Figure 145: Permitted maximum axial displacement of vertical drive shaft with insulator
5.4.6.4.1 Fitting vertical drive shaft with insulator
To fit the vertical drive shaft, proceed as follows.
1.
CAUTION!
Switch off motor protective switch Q1 in the motor-drive
unit (position O). If this is not done, the motor-drive unit may be started in-
advertently and cause injuries.