5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
57
4349322/01 EN
VACUTAP
®
VV
®
2.
NOTICE!
An open kerosene drain plug leads to oil escaping from the oil
compartment and therefore to damage to the on-load tap-changer. Close
kerosene drain plug counter-clockwise (tightening torque 39 Nm).
3. Insert on-load tap-changer insert.
5.2.7 Filling the oil compartment of the on-load tap-changer with
insulating fluid
NOTICE
Damage to the on-load tap-changer!
Unsuitable insulating fluids cause damage to the on-load tap-changer.
► Use insulating fluids that meet the requirements in accordance with IEC
60296.
► If approved by the transformer manufacturer, you can use synthetic es-
ters in accordance with IEC 61099 or natural esters in accordance with
IEC 62770 approved by Maschinenfabrik Reinhausen GmbH.
After drying, completely fill the oil compartment (diverter switch insert fitted)
with insulating fluid again as soon as possible so that an impermissible
amount of humidity is not absorbed from the surroundings.
1. Establish a connecting lead between pipe connection E2 and one of the
pipe connections R, S or Q to ensure equal pressure in the oil compart-
ment and transformer during evacuation.
Figure 40: Connecting lead between E2 and Q
Содержание VACUTAP VV
Страница 1: ...On load tap changer VACUTAP VV Installation and commissioning instructions 4349322 01 EN ...
Страница 112: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 112 4349322 01 EN VACUTAP VV Figure 109 Mounting protective tube ...
Страница 125: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 125 4349322 01 EN VACUTAP VV Figure 125 Angle of deflection α ...
Страница 182: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 182 4349322 01 EN VACUTAP VV 9 Drawings ...
Страница 188: ......
Страница 195: ......
Страница 197: ......