5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
89
4349322/01 EN
VACUTAP
®
VV
®
6. The magnetic field strength (bushings, busbars etc.) must be < 20 kA/m.
Higher field strengths have a negative effect on the function of the protec-
tive relay.
7. The piping from the protective relay to the oil conservator must be routed
with an inclination of at least 2% (1.2°) to ensure the switching gases can
escape freely.
8. The protective relay is intended for a horizontal operating position in close
proximity to the on-load tap-changer head. A positive inclination of up to
5° from horizontal is permitted in the direction to the conservator. An incli-
nation of up to 5° from vertical to either side is permitted.
Figure 81: Protective relay installation