6 Commissioning
Maschinenfabrik Reinhausen GmbH 2020
163
4349322/01 EN
VACUTAP
®
VV
®
2. Establish a connecting lead between pipe connection E2 and one of the
pipe connections R, S or Q to ensure equal pressure in the oil compart-
ment and transformer during evacuation.
Figure 168: Connecting lead
3. Fill on-load tap-changer with new insulating fluid using one of the two free
pipe connections of the on-load tap-changer head.
Figure 169: Pipe connections S and R
4. Take an insulating fluid sample from the oil compartment.
5. Record the temperature of the sample immediately after the sample is
taken.
6. Determine dielectric strength and water content at a sample temperature
of 20 °C ± 5 °C. The dielectric strength and water content must comply
with the limit values specified in the technical data [
6.3.2 Bleeding on-load tap-changer head and suction pipe
6.3.2.1 Bleeding on-load tap-changer head
1. Open all forward and return valves in the pipe system.