6 Commissioning
Maschinenfabrik Reinhausen GmbH 2020
157
4349322/01 EN
VACUTAP
®
VV
®
2. Connect grounding screw of motor-drive protective housing to transformer
tank. It is essential that a CUPAL washer be placed between the cable
shoe and connecting lug. The aluminum side of the CUPAL washer must
be facing the connecting lug.
Figure 165: Grounding screw on motor-drive unit
3. When using a temperature sensor, connect housing of temperature sen-
sor with grounding screw on the on-load tap-changer head or another
grounding point on the transformer. It is essential that a CUPAL washer
be placed between the cable shoe and temperature sensor housing. The
aluminum side of the CUPAL washer must be facing the temperature sen-
sor housing.
Figure 166: Grounding temperature sensor