5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
83
4349322/01 EN
VACUTAP
®
VV
®
2.
NOTICE!
An incomplete tap-change operation may damage the on-load
tap-changer. After operating the diverter switch, continue to crank the
drive shaft of the upper gear unit for 2.5 revolutions in the same direction
in order to correctly complete the tap-change operation.
3. Perform the transformer ratio test.
4. Repeat the transformer ratio test in all operating positions.
5. Switch the on-load tap-changer into adjustment position (see the accom-
panying connection diagram for the on-load tap-changer).
5.4 Fitting protective devices and drive components
5.4.1 Electrically connecting the temperature sensor
Size the cable for the electrical connection of the temperature sensors such
that you can turn the sensors if necessary when mounting the drive shaft.
► Electrically connect the temperature sensors in accordance with the con-
nection diagram provided.
5.4.2 Connecting tap-change supervisory control
1. Ensure that the drive and the on-load tap-changer are in the adjustment
position. You must be able to see a triangle in the tap-change supervisory
control's inspection window.
Figure 71: Tap-change supervisory control
Содержание VACUTAP VV
Страница 1: ...On load tap changer VACUTAP VV Installation and commissioning instructions 4349322 01 EN ...
Страница 112: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 112 4349322 01 EN VACUTAP VV Figure 109 Mounting protective tube ...
Страница 125: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 125 4349322 01 EN VACUTAP VV Figure 125 Angle of deflection α ...
Страница 182: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 182 4349322 01 EN VACUTAP VV 9 Drawings ...
Страница 188: ......
Страница 195: ......
Страница 197: ......