7 Fault elimination
Maschinenfabrik Reinhausen GmbH 2020
173
4349322/01 EN
VACUTAP
®
VV
®
7.2 Tripping the pressure monitoring device and putting the
transformer back into operation
WARNING
Danger of death or severe injury!
Danger of severe injury or death if on-load tap-changer and transformer are
insufficiently tested.
► Be sure to contact Maschinenfabrik Reinhausen to check on-load tap-
changer and transformer after the pressure monitoring device has been
tripped.
► Only use the equipment again when you are sure there is no damage to
the on-load tap-changer or transformer.
If the circuit breaker is tripped by the pressure monitoring device, proceed as
follows:
1. Establish time of tripping.
2. Determine operating position of on-load tap-changer.
3. As a precaution, block the motor-drive unit by tripping the motor protective
switch to prevent the on-load tap-changer from being actuated by remote
control.
4. Check the on-load tap-changer head cover. If insulating fluid is leaking,
close the oil conservator stop valve immediately.
5. Check whether the pressure monitoring device sensor is in the OFF posi-
tion or OPERATION position.
7.2.1 Sensor in the OPERATION position
If the sensor is in the OPERATION position, there may be an error in the trip-
ping circuit. Check the tripping circuit in this case. If you are not able to clar-
ify why the pressure monitoring device tripped, be sure to contact Maschi-
nenfabrik Reinhausen to check the on-load tap-changer.
7.2.2 Sensor in the OFF position
Proceed as follows if the sensor is in the OFF position.
1. Ensure that the transformer is not started up under any circumstances.
Содержание VACUTAP VV
Страница 1: ...On load tap changer VACUTAP VV Installation and commissioning instructions 4349322 01 EN ...
Страница 112: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 112 4349322 01 EN VACUTAP VV Figure 109 Mounting protective tube ...
Страница 125: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 125 4349322 01 EN VACUTAP VV Figure 125 Angle of deflection α ...
Страница 182: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 182 4349322 01 EN VACUTAP VV 9 Drawings ...
Страница 188: ......
Страница 195: ......
Страница 197: ......