5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
99
4349322/01 EN
VACUTAP
®
VV
®
5.4.4.3 Making the electrical connections for the pressure monitoring device
DANGER
Risk of fatal injury due to electrical voltage!
Danger of death due to electrical voltage when assembling and connecting
the device.
► De-energize the device and system peripherals and lock them to prevent
them from being switched back on.
WARNING
Danger of death or severe injury!
Risk of severe injury or death due to improper electrical connection of the
pressure monitoring device.
► Loop the pressure monitoring device into the tripping circuit of the circuit
breakers of the transformer to be protected so that the transformer is im-
mediately de-energized by the circuit breakers when the pressure moni-
toring device is tripped.
► Circuits which only generate an alarm message are not permitted.
1. Remove the cover cap.
2. Insert Use the tapped hole for routing leads for this.
3. Connect the leads to the terminals of the snap-action switch.
The snap-action switch is designed as a normally open and normally
closed switch; it flips after being triggered and can be reset.
4. Connect all of the electrical leads and the protective conductor.
Either 1 or 2 leads can be connected per terminal for the lead connection
(Ø 0.75…2.5 mm²).
5. Secure the cover cap.
6. Ensure the fixing screw is positioned correctly, see also dimensional
drawing supplied.
5.4.5 Fitting motor-drive unit
► Fit motor-drive unit to transformer as described in relevant MR operating
instructions for motor-drive unit.
5.4.6 Fitting drive shaft
Observe the following during mounting:
Resistance to corrosion of components
The square tubes, coupling brackets, coupling bolts, screws, and locking
washers are corrosion-resistant. We therefore recommend not applying the
same external coating to these parts as to the transformer tank.
Содержание VACUTAP VV
Страница 1: ...On load tap changer VACUTAP VV Installation and commissioning instructions 4349322 01 EN ...
Страница 112: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 112 4349322 01 EN VACUTAP VV Figure 109 Mounting protective tube ...
Страница 125: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 125 4349322 01 EN VACUTAP VV Figure 125 Angle of deflection α ...
Страница 182: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 182 4349322 01 EN VACUTAP VV 9 Drawings ...
Страница 188: ......
Страница 195: ......
Страница 197: ......