5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
140
4349322/01 EN
VACUTAP
®
VV
®
18. Fit upper coupling brackets with 3 mm axial clearance.
Figure 143: Fitting upper coupling brackets
19. Working from top to bottom, mount the individual parts of the shaft pro-
tection. Set angle position between both parts of pivotable protective
tube and fix with available hose clip. Secure both upper and lower pro-
tective tubes with a hose clip at both ends. Secure the two telescopic
protective tubes to one another using a hose clip.
The plastic adapters must be at the respective end of the pivotable protec-
tive tube. Only slide telescopic protective tube into upper and lower piv-
otable protective tubes by the width of the adapter before tightening the
hose clips.