5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
36
4349322/01 EN
VACUTAP
®
VV
®
5 Mounting
WARNING
Risk of crushing!
When the on-load tap-changer undertakes a tap-change operation, compo-
nents – some of which are freely accessible – move on the selector,
change-over selector, and potential connection unit. Reaching into the se-
lector, change-over selector, or potential connection unit during a tap-
change operation may result in serious injuries.
► Keep a safe distance of at least 1 m during tap-change operations.
► Do not reach into the selector, change-over selector, or potential connec-
tion unit during tap-change operations.
► Do not switch the on-load tap-changer when working on the selector,
change-over selector, or potential connection unit.
5.1 Preparatory work
Perform the work stated below before installing the on-load tap-changer in
the transformer.
5.1.1 Fitting mounting flange on transformer cover
A mounting flange is required for fitting the on-load tap-changer head on the
transformer cover. This can be supplied as an option or can be produced by
the customer. Mounting flanges made by the customer must comply with the
installation drawings in the appendix.
►
NOTICE!
Fit mounting flange on transformer cover (pressure tight).En-
sure that the sealing face makes complete contact and is not damaged.
Figure 16: Mounting flange
Содержание VACUTAP VV
Страница 1: ...On load tap changer VACUTAP VV Installation and commissioning instructions 4349322 01 EN ...
Страница 112: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 112 4349322 01 EN VACUTAP VV Figure 109 Mounting protective tube ...
Страница 125: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2020 125 4349322 01 EN VACUTAP VV Figure 125 Angle of deflection α ...
Страница 182: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 182 4349322 01 EN VACUTAP VV 9 Drawings ...
Страница 188: ......
Страница 195: ......
Страница 197: ......