5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
85
4349322/01 EN
VACUTAP
®
VV
®
Figure 74: Tap-change supervisory control cover
5.4.3 Installing protective relay in piping and connecting
WARNING
Danger of explosion!
Explosive gases in the protective relay can deflagrate or explode and result
in severe injury or death.
► Wait 15 minutes after switching off the transformer before beginning fur-
ther work on the protective relay so that the gases can dissipate.
► Ensure that there are no ignition sources such as naked flames, hot sur-
faces or sparks (e.g. caused by the build-up of static charge) in the imme-
diate surroundings and that none occur.
► De-energize all auxiliary circuits before beginning work.
► Do not operate any electrical devices during the work (e.g. risk of sparks
from impact wrench).
Always perform all transformer tests with the protective relay attached and
connected.