182
(2) Program condition
This program uses Coincidence output 1 and Coincidence output 2 of CH1 in the high-speed counter module.
The extension output module is used for outputting digital output signals and cam switch output signals.
(3) Initial setting description
(a) Remote buffer memory (parameter area) setting
Setting item
Setting value
Input response time setting
5: 10ms (Initial value)
Output HOLD/CLEAR setting
1: HOLD
Cyclic data update watch time setting
10 (× 100ms)
Comparison output setting
Set a value according to the comparison output function
to be used.
Coincidence output 1 channel assignment setting
0: CH1 (Initial value)
Coincidence output 2 channel assignment setting
0: CH1 (Initial value)
Coincidence output 3 channel assignment setting
1: CH2
Coincidence output 4 channel assignment setting
1: CH2
Coincidence output 1 comparison condition setting
0: Coincidence Output (Initial value)
Coincidence output 2 comparison condition setting
1: Within-range Output
Coincidence output 3 comparison condition setting
0: Coincidence Output (Initial value)
Coincidence output 4 comparison condition setting
0: Coincidence Output (Initial value)
Preset/replace setting at coincidence output (Coincidence output 1)
0: Present value not replaced (Initial value)
Preset/replace setting at coincidence output (Coincidence output 2)
0: Present value not replaced (Initial value)
Cam switch output unit assignment setting
1: Stage 1
Cam switch output 1 channel assignment setting
0: CH1 (Initial value)
Cam switch output 2 channel assignment setting
0: CH1 (Initial value)
Cam switch output 3 channel assignment setting
0: CH1 (Initial value)
Cam switch output 4 channel assignment setting
0: CH1 (Initial value)
Cam switch output 5 channel assignment setting
0: CH1 (Initial value)
Cam switch output 6 channel assignment setting
0: CH1 (Initial value)
Cam switch output 7 channel assignment setting
0: CH1 (Initial value)
Cam switch output 8 channel assignment setting
0: CH1 (Initial value)
Cam switch output 9 channel assignment setting
1: CH2
Cam switch output 10 channel assignment setting
1: CH2
Cam switch output 11 channel assignment setting
1: CH2
Cam switch output 12 channel assignment setting
1: CH2
Cam switch output 13 channel assignment setting
1: CH2
Cam switch output 14 channel assignment setting
1: CH2
Cam switch output 15 channel assignment setting
1: CH2
Cam switch output 16 channel assignment setting
1: CH2
CH1 Operation mode setting
Set a value according to the operation mode to be used.
CH1 Count source selection
0: A Phase/B Phase (Initial value)
CH1 Pulse input mode
3: 2-Phase Multiple of 1
CH1 Counting speed setting
2: 200kpps
CH1 Counter format
Set a value according to the counter format to be used.
CH1 Z phase (Preset) trigger setting
0: Rising (Initial value)