233
CHAPTER 11 TROUBLESHOOTING
11
11.5 T
roub
leshooting for
E
a
ch Pheno
menon
11.5.1
Whe
n the setting
on the oper
ation mode setting is the no
rmal mode
(c) When the preset/replace function by CH
Function input terminal (FUNC1, FUNC2)
cannot be performed
*1
For
Δ
T
1
, refer to the following.
(5) When the counter function selection cannot be performed
(a) When turning on CH
Selected counter function start command (RY25, RY3D) does
not perform the counter function selection
(b) When the input from CH
Function input terminal (FUNC1, FUNC2) does not
perform the counter function selection
Check item
Action
Is the external wiring to CH
Function input terminal (FUNC1,
FUNC2) correct?
Check the external wiring and correct errors.
Is the interval of
Δ
T
1
*1
or longer taken between change in the
setting in CH
Preset value setting (RWw14 to RWw15, RWw2C
to RWw2D) and the execution of preset?
Set the interval of
Δ
T
1
*1
or longer between change in the setting in
CH
Preset value setting (RWw14 to RWw15, RWw2C to RWw2D)
and the execution of preset.
Is CH
External preset/replace (Z Phase) request detection
(RX23, RX3B) off?
Turn off CH
External preset/replace (Z Phase) request detection
(RX23, RX3B) by turning on CH
External preset/replace (Z Phase)
request detection reset command (RY23, RY3B).
Note that the ON/OFF time of CH
External preset/replace (Z Phase)
request detection reset command (RY23, RY3B) must be
Δ
T
1
*1
or
longer. (
Check item
Action
Does the selected function apply to CH
Selected counter
function start command (RY25, RY3D)?
Check referring to the following.
Page 129, Section 8.6
If the selected function is one that starts to work at the rising edge
(OFF to ON) of CH
Selected counter function start command
(RY25, RY3D), is CH
Counter function detection (RX25, RX3D)
used as an interlock?
Turn on or off CH
Selected counter function start command (RY25,
RY3D) using CH
Counter function detection (RX25, RX3D) as an
interlock.
Is CH
Function input terminal (FUNC1, FUNC2) off?
Turn off CH
Function input terminal (FUNC1, FUNC2).
Check item
Action
Is the external wiring to CH
Function input terminal (FUNC1,
FUNC2) correct?
Check the external wiring and correct errors.
Is CH
Selected counter function start command (RY25, RY3D)
off?
Turn off CH
Selected counter function start command (RY25,
RY3D).
Содержание NZ2GFCF-D62PD2