210
0140
H
Minor error
Non-volatile
memory data
error
(error history)
The error history data
stored in the nonvolatile
memory are abnormal.
*1
• The module recovers
automatically soon after this
error occurred. However, the
preceding error history data
are erased.
• Take measures against
noise, such as using a
shielded cable for
connection.
• If the same error occurs
again, a module failure may
be the cause. Please consult
your local Mitsubishi
representative.
0150
H
Minor error
Remote buffer
memory access
error
The REMFR/REMTO
instruction has accessed
the range outside the
remote buffer memory
range.
*1
Correct the REMFR/REMTO
instruction setting so that the
instruction accesses the range
within the remote buffer
memory range.
0160
H
Minor error
Station number
switch change
failure
The setting on the station
number setting switch has
been changed while the
module power supply is
on.
*1
Set the switch back to the
station number which was set
when the module was powered
on.
0330
H
Moderate error
Number of ON
times
integration
function setting
error
The number of ON times
integration function is
enabled when the cam
switch function is selected.
*13
Set Number of ON times
integration function enable
(address: 0202
H
) to 0000
H
, and
turn off then on Initial data
setting request flag (RY9).
0340
H
Moderate error
Cam switch
output unit
assignment
setting error
A value other than 0 and 1
is set in Cam switch output
unit assignment setting
(address: 0104
H
).
*13
Set Cam switch output unit
assignment setting (address:
0104
H
) to 0 or 1, and turn off
then on Initial data setting
request flag (RY9).
0800
H
Moderate error
Comparison
output setting
error
The setting in Comparison
output setting (address:
0100
H
) is in one of the
following cases.
• A value other than 0 and
1 is set.
• If 1 is set, the value in
CH
Operation mode
setting (address: 0120
H
,
0140
H
) is other than 0.
*13
Take the following actions, and
turn off then on Initial data
setting request flag (RY9).
• Set Comparison output
setting (address: 0100
H
) to 0
or 1.
• Set CH
Operation mode
setting (address: 0120
H
,
0140
H
) to 0.
0850
H
Moderate error
Cyclic data
update watch
time setting
error
A value other than 0 to 20
is set in Cyclic data update
watch time setting
(address: 0003
H
).
*13
Set Cyclic data update watch
time setting (address: 0003
H
) to
a value between 0 and 20, and
turn off then on Initial data
setting request flag (RY9).
0F40
H
Moderate error
Input response
time setting
error
The lower 3 bits of Input
response time setting
(address: 0001
H
) is set to
000b, 001b, or 010b.
*13
Set the lower 3 bits of Input
response time setting (address:
0001
H
) to a value other than
000b, 001b, and 010b, then
turn on Initial data setting
request flag (RY9).
1341
H
Moderate error
Cam switch
output unit
assignment
error
An extension output
module does not exist
where Cam switch output
unit assignment setting
(address: 0104
H
) assigns
the module.
*13
Power off the module, and
connect an extension output
module where Cam switch
output unit assignment setting
(address: 0104
H
) assigns the
module. Then power on the
module.
Error code
(hexadecimal)
Classification
Error name
Description and
cause
Operation of when an error
occurs
Action
Error CH
The other
CHs