255
APPENDICES
A
Appendix 2 Details of R
emote Registers
Appendix 2
Details of Remote Registers
The following shows details of remote registers.
(1) Remote registers (RWr0 to RWr1)
Address
(RWr)
Name
Description
Default
CH1 CH2
0
Counter value
greater/smaller signal
• When the coincidence output function is selected and Coincidence output
comparison condition setting (address: 0102
H
) is set to "Coincidence Output
(00)", this area stores the magnitude relation between the values in Point
setting (Coincidence output 1 to 4) (RWw0 to RWw1, RWw4 to RWw5, RWw8
to RWw9, RWwC to RWwD) and CH
Present value (RWr10 to RWr11,
RWr28 to RWr29).
Point setting (Coincidence output 1 to 4) > Present value ... Counter value
greater: 0/Counter value smaller: 1
Point setting (Coincidence output 1 to 4) = Present value ... Counter value
greater: 0/Counter value smaller: 0
Point setting (Coincidence output 1 to 4) < Present value ... Counter value
greater: 1/Counter value smaller: 0
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
0000
H
1
EQU1 to EQU4
terminal status
• This area stores the statuses of the coincidence output 1 to 4 terminals (EQU1
to EQU4).
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
0000
H
b15
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
Coincidence
output 4
0
0
0
0
0
0
0
0
-
-
-
-
-
-
-
-
0 (fixed)
Coincidence
output 3
Coincidence
output 2
Coincidence
output 1
Counter
value
greater
Counter
value
smaller
Counter
value
greater
Counter
value
smaller
Counter
value
greater
Counter
value
smaller
Counter
value
greater
Counter
value
smaller
b15
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
0
0
0
0
0
0
0
0
EQU1
EQU2
EQU3
EQU4
0
0
0
0
0 (fixed)
0: OFF
1: ON
Содержание NZ2GFCF-D62PD2
Страница 1: ......
Страница 2: ......
Страница 54: ...52 Memo ...
Страница 206: ...204 Memo ...
Страница 303: ......
Страница 304: ......