113
CHAPTER 8 FUNCTIONS
8
8.3 C
ompariso
n Outp
ut Function
8.3.2 C
oincidence output fun
ction
●
Coincidence output 1 to 4 (RX10 to RX13) turn on regardless of CH
Coincidence output enable command (RY20,
RY38).
●
Even if Lower limit value setting (Coincidence output 1 to 4) (RWw0 to RWw1, RWw4 to RWw5, RWw8 to RWw9, RWwC
to RWwD) and Upper limit value setting (Coincidence output 1 to 4) (RWw2 to RWw3, RWw6 to RWw7, RWwA to RWwB,
RWwE to RWwF) are changed, the present value is not compared with the changed value unless Setting change request
(Coincidence output 1 to 4) (RY14 to RY17) is turned off then on.