273
APPENDICES
A
Appendix 3 Details of R
emote Buffer
Memory Addresses
(10)Module-based parameter data (address: 0129
H
, 0149
H
)
Address
Name
Description
Default
CH1
CH2
0129
H
0149
H
External control
input response time
setting
• Set the input response time of CH
Phase Z input terminal (Z1, Z2), CH
Function input terminal (FUNC1, FUNC2), and CH
Latch counter input
terminal (LATCH1, LATCH2).
• The following shows the setting range.
002A
H
1) Z phase input response time setting
Setting
OFF
→
ON
Response time
ON
→
OFF
Response time
00
0.25µs
2.5µs
01
0.1ms
0.1ms
10
1.0ms
1.0ms
2) Function input response time setting
Setting
OFF
→
ON
Response time
ON
→
OFF
Response time
00
0.02ms
0.1ms
01
0.1ms
0.1ms
10
1.0ms
1.0ms
3) Latch counter input response time setting
Setting
OFF
→
ON
Response time
ON
→
OFF
Response time
00
0.02ms
0.1ms
01
0.1ms
0.1ms
10
1.0ms
1.0ms
• When CH
Function input logic setting (address: 0127
H
, 0147
H
) and CH
Latch counter input logic setting (address: 0128
H
, 0148
H
) are set to
Negative Logic (1), the OFF
→
ON response time and the ON
→
OFF
response time invert. For example, when CH
Latch counter input logic
setting (address: 0128
H
, 0148
H
) is set to Negative Logic (1) and
corresponding bits for this area are set to 00, the OFF
→
ON response time
is 0.1ms.
• The reflection timing of the setting value
When Initial data setting request flag (RY9) is turned off then on
b15
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
0
0
0
0
0
0
0
0
2)
3)
1)
0
0
0 (fixed)