219
CHAPTER 11 TROUBLESHOOTING
11
11.2 Er
ror
Code List
812
H
Moderate error
CH
Count
source
coincidence
output setting
error
Either of the following
cases is the cause if the
value in CH
Operation
mode setting (address:
0120
H
, 0140
H
) is 0, and
the value in CH
Count
source selection (address:
0121
H
, 0141
H
) is 1 or 2.
• A value other than 0 and
4 is set in CH
Operation mode setting
(address: 0120
H
,
0140
H
) of the other
channel.
• A channel where CH
Count source selection
(address: 0121
H
,
0141
H
) is set is the
same as the channel
assigned to the
corresponding bit of
Coincidence output
channel assignment
setting (address:
0101
H
).
indicates the channel
where settings are
incorrect.
*13
Take the following actions, and
turn off then on Initial data
setting request flag (RY9).
• Set CH
Operation mode
setting (address: 0120
H
,
0140
H
) for the other channel
to 0 or 4.
• Set the corresponding bit of
Coincidence output channel
assignment setting (address:
0101
H
) to the channel where
CH
Count source selection
(address: 0121
H
, 0141
H
) is
not set.
813
H
Moderate error
CH
Pulse
input mode
setting error
A value other than 0 to 5 is
set in CH
Pulse input
mode (address: 0122
H
,
0142
H
).
indicates the channel
where settings are
incorrect.
*13
Set CH
Pulse input mode
(address: 0122
H
, 0142
H
) to a
value between 0 and 5, and
turn off then on Initial data
setting request flag (RY9).
814
H
Moderate error
CH
Counting
speed setting
error
The setting in CH
Counting speed setting
(address: 0123
H
, 0143
H
)
is in one of the following
cases.
• If the value in CH
Pulse input mode
(address: 0122
H
,
0142
H
) is 0, 2, or 3, a
value other than 0 to 5 is
set.
• If the value in CH
Pulse input mode
(address: 0122
H
,
0142
H
) is 1 or 4, a value
other than 0 to 6 is set.
• If the value in CH
Pulse input mode
(address: 0122
H
,
0142
H
) is 5, a value
other than 0 to 7 is set.
indicates the channel
where settings are
incorrect.
*13
Take one of the following
actions on CH
Counting
speed setting (address: 0123
H
,
0143
H
), and turn off then on
Initial data setting request flag
(RY9).
• If the value in CH
Pulse
input mode (address: 0122
H
,
0142
H
) is 0, 2, or 3, set a
value between 0 and 5.
• If the value in CH
Pulse
input mode (address: 0122
H
,
0142
H
) is 1 or 4, set a value
between 0 and 6.
• If the value in CH
Pulse
input mode (address: 0122
H
,
0142
H
) is 5, set a value
between 0 and 7.
Error code
(hexadecimal)
Classification
Error name
Description and
cause
Operation of when an error
occurs
Action
Error CH
The other
CHs
Содержание NZ2GFCF-D62PD2