104
(2) Comparison condition types and setting
Depending on the selected comparison condition, the range to be compared with the present value differs.
(a) Coincidence output
Coincidence output 1 to 4 turn on when CH
Present value (RWr10 to RWr11, RWr28 to RWr29) matches with
a point set in Point setting (Coincidence output 1 to 4) (RWw0 to RWw1, RWw4 to RWw5, RWw8 to RWw9,
RWwC to RWwD).
(b) Within-range output
Coincidence output 1 to 4 turn on when both the following conditions are satisfied.
• When CH
Present value (RWr10 to RWr11, RWr28 to RWr29) is Lower limit value setting (Coincidence
output 1 to 4) (RWw0 to RWw1, RWw4 to RWw5, RWw8 to RWw9, RWwC to RWwD) or more
• When CH
Present value (RWr10 to RWr11, RWr28 to RWr29) is Upper limit value setting (Coincidence
output 1 to 4) (RWw2 to RWw3, RWw6 to RWw7, RWwA to RWwB, RWwE to RWwF) or less
(c) Out-of-range output
Coincidence output 1 to 4 turn on when either of the following conditions is satisfied.
• When CH
Present value (RWr10 to RWr11, RWr28 to RWr29) is less than Lower limit value setting
(Coincidence output 1 to 4) (RWw0 to RWw1, RWw4 to RWw5, RWw8 to RWw9, RWwC to RWwD)
• When CH
Present value (RWr10 to RWr11, RWr28 to RWr29) exceeds Upper limit value setting
(Coincidence output 1 to 4) (RWw2 to RWw3, RWw6 to RWw7, RWwA to RWwB, RWwE to RWwF)
Coincidence
output
Coincidence output 1 to 4
(RX10 to RX13)
Coincidence output 1 to 4
terminals (EQU1 to EQU4)
OFF
ON
Point setting (Coincidence output 1 to 4)
(RWw0 to RWw1, RWw4 to RWw5,
RWw8 to RWw9, RWwC to RWwD)
Present
value
* To turn off Coincidence output 1 to 4 (RX10 to RX13),
use Reset command (Coincidence output 1 to 4) (RY10 to RY13).
Within-range
output
Out-of-range
output
Coincidence output 1 to 4
(RX10 to RX13)
Coincidence output 1 to 4 terminals
(EQU1 to EQU4)
Coincidence output 1 to 4
(RX10 to RX13)
Coincidence output 1 to 4 terminals
(EQU1 to EQU4)
Lower limit value setting
(Coincidence output 1 to 4)
(RWw0 to RWw1, RWw4 to RWw5,
RWw8 to RWw9, RWwC to RWwD)
Upper limit value setting
(Coincidence output 1 to 4)
(RWw2 to RWw3, RWw6 to RWw7,
RWwA to RWwB, RWwE to RWwF)
Present value
OFF
ON
OFF
ON