CHAPTER 8 FUNCTIONS
8
8.3 C
ompariso
n Outp
ut Function
8.3.2 C
oincidence output fun
ction
8.3.2
Coincidence output function
The coincidence output function compares CH
Present value (RWr10 to RWr11, RWr28 to RWr29) with a
coincidence detection point or with an area divided by the coincidence output upper/lower limit value, and outputs the
comparison result from Coincidence output 1 to 4 terminals (EQU1 to EQU4). At coincidence output, Coincidence
output 1 to 4 (RX10 to RX13) turns on.
The unit to output the comparison result is called coincidence output.
Four points are assigned to coincidence output. The present value is compared with each point and the comparison
result is output from the point.
(1) Setting method of the coincidence output function
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Select a high-speed counter module in "List of stations"
[CC IE Field Configuration]
[Parameter Processing of Slave Station]
2.
Set "0: Coincidence Output Function" for "Comparison output setting".
3.
Set a channel to be compared for "Coincidence output 1 to 4 channel assignment setting".
4.
Set the comparison condition for "Coincidence output 1 to 4 comparison condition setting".
When "Operation mode setting" is set to a mode other than "0: Normal Mode", the setting of "Coincidence output 1 to 4
comparison condition setting" is ignored.