37
CHAPTER 3 SPECIFICATIONS
3
3.5 List of Remote
I/O Signals
Main
module
RX30
Use prohibited
RY30
CH1 Pulse measurement start command
(Function input terminal)
RX31
CH1 Measured pulse value update flag reset
completed (Function input terminal)
RY31
CH1 Measured pulse value update flag reset
command (Function input terminal)
RX32
CH1 Measured pulse value update flag
(Function input terminal)
RY32
CH1 Pulse measurement start command
(Latch counter input terminal)
RX33
CH1 Measured pulse value update flag reset
completed (Latch counter input terminal)
RY33
CH1 Measured pulse value update flag reset
command (Latch counter input terminal)
RX34
CH1 Measured pulse value update flag
(Latch counter input terminal)
RY34
Use prohibited
RX35
CH1 ON width setting change completed
(PWM output)
RY35
CH1 ON width setting change request
(PWM output)
RX36
CH1 Error status
RY36
CH1 Error reset command
RX37
CH1 Warning status
RY37
Use prohibited
RX38
Use prohibited
RY38
CH2 Coincidence output enable command
RX39
CH2 Preset/replace completion
RY39
CH2 Preset/replace command
RX3A
Use prohibited
RY3A
CH2 Count down command
RX3B
CH2 External preset/replace (Z Phase) request
detection
RY3B
CH2 External preset/replace (Z Phase) request
detection reset command
RX3C
Use prohibited
RY3C
CH2 Count enable command
RX3D
CH2 Counter function detection
RY3D
CH2 Selected counter function start command
RX3E
CH2 Cam switch execute/PWM output
RY3E
CH2 Cam switch execute command/PWM
output start command
RX3F
CH2 Setting change completed
(Sampling counter/Periodic pulse counter)
RY3F
CH2 Setting change request
(Sampling counter/Periodic pulse counter)
RX40
CH2 Update flag reset completed (Latch count
value/Sampling count value/Periodic pulse
count value)
RY40
CH2 Update flag reset command (Latch count
value/Sampling count value/Periodic pulse
count value)
RX41
CH2 Update flag (Latch count value/Sampling
count value/Periodic pulse count value)
RY41
Use prohibited
RX42
CH2 Latch count value update flag reset
completed (Latch counter input terminal)
RY42
CH2 Latch count value update flag reset
command (Latch counter input terminal)
RX43
CH2 Latch count value update flag
(Latch counter input terminal)
RY43
Use prohibited
RX44
CH2 Update flag reset completed (Measured
frequency value/Measured rotation speed value)
RY44
CH2 Update flag reset command (Measured
frequency value/Measured rotation speed value)
RX45
CH2 Update flag (Measured frequency
value/Measured rotation speed value)
RY45
Use prohibited
RX46
Use prohibited
RY46
Use prohibited
RX47
Use prohibited
RY47
Use prohibited
Module
type
Remote input signal direction: High-speed counter
module
→
Master/local module
Remote output signal direction: Master/local
module
→
High-speed counter module
Device
number
Description
Device
number
Description
Содержание NZ2GFCF-D62PD2
Страница 1: ......
Страница 2: ......
Страница 54: ...52 Memo ...
Страница 206: ...204 Memo ...
Страница 303: ......
Страница 304: ......