CHAPTER 8 FUNCTIONS
8
8.17 Output
HOL
D
/CLEAR Setting Fu
nction
8.17
Output HOLD/CLEAR Setting Function
When the high-speed counter module is disconnected from data link, or the CPU module operating status is STOP,
whether to hold or clear the last Coincidence output (EQU1 to EQU4) and the output status of the extension output
module can be set. Set whether to hold or clear the values for all the output points of the module in a batch from the
module parameter setting window of GX Works2 or the program.
(1) Output HOLD/CLEAR setting and its operation
The following table lists the ON/OFF status of when HOLD or CLEAR is set for an output.
(2) Setting method
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Select a high-speed counter module in "List of stations"
[CC IE Field Configuration]
[Parameter Processing of Slave Station]
2.
For "Output HOLD/CLEAR setting", select "0: CLEAR" or "1: HOLD".
When the output status changes according to the change in the comparison result after the output is set to HOLD, the output
of the following functions changes.
• Coincidence output (EQU1 to EQU4) of the coincidence output function
• Coincidence output (EQU1 to EQU4) of the PWM output function
• Output of the extension output module that is used as the output of the cam switch function (Y0 to YF)
Operating status
"Output HOLD/CLEAR setting"
"0: CLEAR" (default)
"Output HOLD/CLEAR setting"
"1: HOLD"
Last output
status OFF
Last output
status ON
Last output
status OFF
Last output
status ON
Data link in
operation
CPU module in RUN
OFF
ON
OFF
ON
CPU module in STOP
OFF
OFF
OFF
ON
CPU module in PAUSE
OFF
ON
OFF
ON
CPU module in RESET
OFF
OFF
OFF
ON
During disconnection/cyclic stop
OFF
OFF
OFF
ON
Item
Setting range
Output HOLD/CLEAR setting
• 0: CLEAR
• 1: HOLD