274
(11)Module-based parameter data (address: 012A
H
to 012B
H
, 014A
H
to 014B
H
)
(12)Module-based monitoring data (address: 0600
H
)
Address
Name
Description
Default
CH1
CH2
012A
H
014A
H
Pulse measurement
setting (Function
input terminal)
• Set the pulse measurement target of CH
Function input terminal
(FUNC1, FUNC2).
• The following shows the setting range.
0: Pulse ON Width
1: Pulse OFF Width
• The reflection timing of the setting value
When Initial data setting request flag (RY9) is turned off then on
0
012B
H
014B
H
Pulse measurement
setting (Latch
counter input
terminal)
• Set the pulse measurement target of CH
Latch counter input terminal
(LATCH1, LATCH2).
• The following shows the setting range.
0: Pulse ON Width
1: Pulse OFF Width
• The reflection timing of the setting value
When Initial data setting request flag (RY9) is turned off then on
0
Address
Name
Description
Default
0600
H
Channel assignment
(Coincidence output
1 to 4)
• This area stores the channel assignment statuses of coincidence outputs.
• The following shows the range of values which can be stored.
• When Initial data setting request flag (RY9) is turned off then on, the value in
this area is cleared.
0000
H
b15
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
Coincidence
output 4
0
0
0
0
0
0
0
0
0 (fixed)
00: No Assignment
01: CH1
10: CH2
Coincidence
output 3
Coincidence
output 2
Coincidence
output 1