42
*1
For the REMFR and REMTO instructions, refer to the following.
User's manual for the master/local module used
*2
For the access method, refer to the following.
• Parameter area (
• Error history area (
Do not access the system area using the REMFR or REMTO instruction. Doing so may cause the module to malfunction.
(1) Parameter area (address: 0000
H
to 04FF
H
)
For the parameter area, parameters can be set using the CC IE Field configuration of GX Works2 or using the
REMTO instruction.
The parameter in the parameter area is backed up to the nonvolatile memory.
The parameter backed up to the nonvolatile memory is read to the parameter area when the module power
supply is turned off then on or the module returns from remote reset.
If the parameter is written from the parameter setting of the CC IE Field configuration of GX Works2, it is also
written to the nonvolatile memory at that time. When the parameter is written using the REMTO instruction, it is
written to the nonvolatile memory when Initial data setting request flag (RY9) is turned off then on. At this time,
the parameter is written to the nonvolatile memory even though it is incorrect. When the power supply is turned
off then on with an incorrect parameter written, the incorrect parameter is read from the nonvolatile memory and
an error code is stored to CH
Latest error code (RWr22, RWr3A). Take corrective action according to the error
code list. (
Type
Address
Description
Default
*1
Read/
Write
*2
Decimal
Hexadecimal
Station-based
parameter data
0
0000
H
System area
⎯
⎯
1
0001
H
Input response time setting
0005
H
R/W
2
0002
H
Output HOLD/CLEAR setting
0000
H
R/W
3
0003
H
Cyclic data update watch time setting
0
R/W
4 to 255
0004
H
to 00FF
H
System area
⎯
⎯
Module-based
parameter data
(main module)
256
0100
H
Comparison output setting
0
R/W
257
0101
H
Coincidence output channel assignment setting
0000
H
R/W
258
0102
H
Coincidence output comparison condition setting
0000
H
R/W
259
0103
H
Preset/replace setting at coincidence output
0000
H
R/W
260
0104
H
Cam switch output unit assignment setting
0
R/W
261
0105
H
Cam switch output channel assignment setting
0000
H
R/W
262 to 287
0106
H
to 011F
H
System area
⎯
⎯
288
0120
H
CH1 Operation mode setting
0
R/W
289
0121
H
CH1 Count source selection
0
R/W
290
0122
H
CH1 Pulse input mode
0
R/W
291
0123
H
CH1 Counting speed setting
0
R/W
292
0124
H
CH1 Counter format
0
R/W
293
0125
H
CH1 Phase Z setting
0000
H
R/W
294
0126
H
CH1 Counter function selection
0
R/W
295
0127
H
CH1 Function input logic setting
0
R/W
Содержание NZ2GFCF-D62PD2