243
APPENDICES
A
Appendix 1 Details of R
emote I/O Signa
ls
Appendix 1.1 Details of r
emote input sig
nals
RX28
Update flag
reset completed
(Latch count
value)
• This signal turns on when resetting CH
Update flag (Latch count value) (RX29, RX41) by
CH
Update flag reset command (Latch count value) (RY28, RY40) is completed.
• This signal turns off when CH
Update flag reset command (Latch count value) (RY28,
RY40) is turned off.
CH1
RX40
CH2
Update flag
reset completed
(Sampling count
value)
• This signal turns on when resetting CH
Update flag (Sampling count value) (RX29, RX41)
by CH
Update flag reset command (Sampling count value) (RY28, RY40) is completed.
• This signal turns off when CH
Update flag reset command (Sampling count value) (RY28,
RY40) is turned off.
(The operation is the same as that of CH
Update flag reset completed (Latch count value)
(RX28, RX40) except the signal name.)
Update flag
reset completed
(Periodic pulse
count value)
• This signal turns on when resetting CH
Update flag (Periodic pulse count value) (RX29,
RX41) by CH
Update flag reset command (Periodic pulse count value) (RY28, RY40) is
completed.
• This signal turns off when CH
Update flag reset command (Periodic pulse count value)
(RY28, RY40) is turned off.
(The operation is the same as that of CH
Update flag reset completed (Latch count value)
(RX28, RX40) except the signal name.)
Remote input
(RX) No.
Signal name
Description
CH Update flag reset command
(Latch count value)
(RY28, RY40)
CH Update flag (Latch count value)
(RX29, RX41)
CH Update flag reset completed
(Latch count value)
(RX28, RX40)
Controlled by the high-speed counter module
Controlled by the program
ON
OFF
ON
OFF
ON
OFF