12. COMMUNICATION FUNCTION (MITSUBISHI ELECTRIC GENERAL-PURPOSE AC SERVO PROTOCOL)
12 - 16
(2) Writing processed data
When the data to be written is handled as decimal, the decimal point position must be specified. If it is
not specified, the data cannot be written. When the data is handled as hexadecimal, specify "0" as the
decimal point position.
The data to be sent is the following value.
Decimal point position
0: No decimal point
1: First least significant digit
2: Second least significant digit
3: Third least significant digit
4: Forth least significant digit
5: Fifth least significant digit
0
Data is transferred in hexadecimal.
For example, here is described how to process the set data when a value of "15.5" is sent.
Since the decimal point position is the second least significant digit, the decimal point position data is
"2".
As the data to be sent is hexadecimal, convert the decimal data into hexadecimal.
155
→
9B
Hence, "0200009B" is transmitted.