5. PARAMETERS
5 - 16
No./symbol/
name
Setting
digit
Function
Initial
value
[unit]
Control mode
P S T
PA21
*AOP3
Function
selection A-3
_ _ _ x One-touch tuning function selection
0: Disabled
1: Enabled
When the digit is "0", the one-touch tuning is not available.
1h
_ _ x _ For manufacturer setting
0h
_ x _ _
0h
x _ _ _ Electronic gear selection
0: Electronic gear ([Pr. PA06] and [Pr. PA07])
1: Number of command input pulses per revolution ([Pr. PA05])
0h
PA23
DRAT
Drive
recorder
arbitrary
alarm trigger
setting
_ _ x x Alarm detail No. setting
Set the digits when you execute the trigger with arbitrary alarm detail No. for the
drive recorder function.
When these digits are "0 0", only the arbitrary alarm No. setting will be enabled.
00h
x x _ _ Alarm No. setting
Set the digits when you execute the trigger with arbitrary alarm No. for the drive
recorder function.
When "0 0" are set, arbitrary alarm trigger of the drive recorder will be disabled.
00h
Setting example:
To activate the drive recorder when [AL. 50 Overload 1] occurs, set "5 0 0 0".
To activate the drive recorder when [AL. 50.3 Thermal overload error 4 during operation] occurs, set "5 0 0 3".
PA24
AOP4
Function
selection A-4
_ _ _ x Vibration suppression mode selection
0: Standard mode
1: 3 inertia mode
2: Low response mode
When you select the standard mode or low response mode, "Vibration suppression
control 2" is not available.
When you select the 3 inertia mode, the feed forward gain is not available.
Before changing the control mode during the 3 inertia mode or low response mode,
stop the motor.
0h
_ _ x _ For manufacturer setting
0h
_ x _ _
0h
x _ _ _
0h
PA25
OTHOV
One-touch
tuning -
Overshoot
permissible
level
Set a permissible value of overshoot amount for one-touch tuning as a percentage of
the in-position range.
However, setting "0" will be 50%.
Setting range: 0 to 100
0
[%]
PA26
*AOP5
Function
selection A-5
_ _ _ x Torque limit function selection at instantaneous power failure
0: Disabled
1: Enabled
Selecting "1" for this digit will limit torques to save electric energy when an
instantaneous power failure occurs during operation and will make [AL. 10
Undervoltage] less likely to occur.
The torque limit function at instantaneous power failure is enabled when
"Instantaneous power failure tough drive selection" in [Pr. PA20] is "Enabled (_ 1 _
_)".
0h
_ _ x _ For manufacturer setting
0h
_ x _ _
0h
x _ _ _
0h
Содержание MR-JE-_A
Страница 9: ...A 8 MEMO ...
Страница 15: ...6 MEMO ...
Страница 29: ...1 FUNCTIONS AND CONFIGURATION 1 14 MEMO ...
Страница 139: ...4 STARTUP 4 38 MEMO ...
Страница 187: ...5 PARAMETERS 5 48 MEMO ...
Страница 221: ...6 NORMAL GAIN ADJUSTMENT 6 34 MEMO ...
Страница 259: ...8 TROUBLESHOOTING 8 8 MEMO ...
Страница 264: ...9 DIMENSIONS 9 5 2 SCR connector system 3M Receptacle 36210 0100PL Shell kit 36310 3200 008 Unit mm 34 8 39 5 22 4 11 0 ...
Страница 265: ...9 DIMENSIONS 9 6 MEMO ...
Страница 273: ...10 CHARACTERISTICS 10 8 MEMO ...
Страница 339: ...12 COMMUNICATION FUNCTION MITSUBISHI ELECTRIC GENERAL PURPOSE AC SERVO PROTOCOL 12 34 MEMO ...