11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 8
(1) MR-JE-100A or less
When you use a regenerative option for MR-JE-40A to MR-JE-100A, remove wirings of P+ and C,
remove the built-in regenerative resistor, and then connect the regenerative option between P+ and C.
G3 and G4 are terminals for thermal sensor. Between G3 and G4 is opened when the regenerative
option overheats abnormally.
Always remove the wiring (across P+ to C) of the
servo amplifier built-in regenerative resistor.
P+
C
G4
G3
C
P
Regenerative option
5 m or less
Servo amplifier
(Note 2)
(Note 1)
Cooling fan
(Note 3)
Note 1. The built-in regenerative resistor is not provided for MR-JE-10A and MR-JE-20A.
2. Make up a sequence which will switch off the magnetic contactor when abnormal
heating occurs.
G3-G4 contact specifications
Maximum voltage: 120 V AC/DC
Maximum current: 0.5 A/4.8 V DC
Maximum capacity: 2.4 VA
3. When the ambient temperature is more than 55 °C and the regenerative load ratio
is more than 60% in MR-RB32, forcefully cool the air with a cooling fan (1.0
m
3
/min or more, 92 mm × 92 mm). A cooling fan is not required if the ambient
temperature is 35 °C or less. (A cooling fan is required for the shaded area in the
following graph.)
100
60
0
0
Ambient temperature [°C]
35
55
A cooling fan is
not required.
A cooling fan is required.
Load r
atio [%]
Содержание MR-JE-_A
Страница 9: ...A 8 MEMO ...
Страница 15: ...6 MEMO ...
Страница 29: ...1 FUNCTIONS AND CONFIGURATION 1 14 MEMO ...
Страница 139: ...4 STARTUP 4 38 MEMO ...
Страница 187: ...5 PARAMETERS 5 48 MEMO ...
Страница 221: ...6 NORMAL GAIN ADJUSTMENT 6 34 MEMO ...
Страница 259: ...8 TROUBLESHOOTING 8 8 MEMO ...
Страница 264: ...9 DIMENSIONS 9 5 2 SCR connector system 3M Receptacle 36210 0100PL Shell kit 36310 3200 008 Unit mm 34 8 39 5 22 4 11 0 ...
Страница 265: ...9 DIMENSIONS 9 6 MEMO ...
Страница 273: ...10 CHARACTERISTICS 10 8 MEMO ...
Страница 339: ...12 COMMUNICATION FUNCTION MITSUBISHI ELECTRIC GENERAL PURPOSE AC SERVO PROTOCOL 12 34 MEMO ...