11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Precautions for wiring
The cables between the servo amplifier and the brake unit, and between the resistor unit and the brake unit
should be as short as possible. Always twist the cable longer than 5m (twist five times or more per one
meter). Even when the cable is twisted, the cable should be less than 10m. Using cables longer than 5m
without twisting or twisted cables longer than 10m, may result in the brake unit malfunction.
Servo amplifier
Brake unit
5m or less
5m or less
Servo amplifier
Brake unit
10m or less
10m or less
P( )
N( )
P
N
P
PR
PR
P
N
P
PR
P
PR
Twist
Resistor unit
Resistor unit
P( )
N( )
Twist
P
(4) Cables
(a) Cables for the brake unit
For the brake unit, HIV cable (600V grade heat-resistant PVC insulated wire) is recommended.
1) Main circuit terminal
Cable size
Crimping
terminal
N/ , P/ , PR,
Brake unit
Main
circuit
terminal
screw
size
N/ , P/ ,
PR,
Tightening
torque
HIV cables,
etc. [mm
2
]
AWG
200V
FR-BU2-15K
M4 5.5-4 1.5 3.5
12
class
FR-BU2-30K
M5 5.5-5 2.5 5.5
10
FR-BU2-55K
M6
14-6
4.4
14
6
400V
FR-BU2-H30K
M4 5.5-4 1.5 3.5
12
class
FR-BU2-H55K
M5 5.5-5 2.5 5.5
10
N/
P/
PR
Terminal block
FR-BU2-H75K M6
14-6
4.4
14
6
Содержание Melservo MR-J3- 350B4
Страница 15: ...A 14 MEMO ...
Страница 21: ...6 MEMO ...
Страница 107: ...3 52 3 SIGNALS AND WIRING MEMO ...
Страница 171: ...7 16 7 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 181: ...8 10 8 TROUBLESHOOTING MEMO ...
Страница 193: ...9 12 9 OUTLINE DRAWINGS MEMO ...
Страница 295: ...12 4 12 ABSOLUTE POSITION DETECTION SYSTEM 2 For MR J3 500B or more MR J3 350B4 or more Insert connector into CN4 ...
Страница 297: ...12 6 12 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...
Страница 397: ...13 100 13 SERVO AMPLIFIERS WITH A LARGE CAPACITY 30k TO 55kW MEMO ...