11 - 80
11. OPTIONS AND AUXILIARY EQUIPMENT
(d) Line noise filter (FR-BSF01, FR-BLF)
This filter is effective in suppressing noises radiated from the power supply side and output side of the
servo amplifier and also in suppressing high-frequency leakage current (zero-phase current) especially
within 0.5MHz to 5MHz band.
Connection diagram
Outline drawing [Unit: mm]
FR-BSF01 (for wire size 3.5mm
2
(AWG12) or less))
4.
5
Approx.110
95 0.5
A
p
pr
o
x.
22
.5
A
pp
ro
x.
65
Approx.65
33
2- 5
Use the line noise filters for wires of the main power supply (L
1
L
2
L
3
) and of the motor power supply (U V W). Pass each of the
3-phase wires through the line noise filter an equal number of
times in the same direction. For the main power supply, the effect
of the filter rises as the number of passes increases, but generally
four passes would be appropriate. For the motor power supply,
passes must be four times or less. Do not pass the grounding
(earth) wire through the filter, or the effect of the filter will drop.
Wind the wires by passing through the filter to satisfy the required
number of passes as shown in Example 1. If the wires are too
thick to wind, use two or more filters to have the required number
of passes as shown in Example 2. Place the line noise filters as
close to the servo amplifier as possible for their best performance.
Example 2
Two filters are used
(Total number of turns: 4)
Power
supply
Servo amplifier
Line noise
filter
NFB
L
3
L
1
L
2
Example 1
(Number of turns: 4)
Power
supply
NFB
L
1
L
2
L
3
Servo amplifier
Line noise
filter
MC
MC
FR-BLF(for wire size 5.5mm
2
(AWG10) or more))
160
180
130
85
80
2
.3
35
7
3
1.
5
7
(e) Radio noise filter (FR-BIF-(H))
This filter is effective in suppressing noises radiated from the power supply side of the servo amplifier
especially in 10MHz and lower radio frequency bands. The FR-BIF (-H) is designed for the input only.
Connection diagram
Outline drawing (Unit: mm)
Make the connection cables as short as possible.
Grounding is always required.
When using the FR-BIF with a single-phase power
supply, always insulate the wires that are not used
for wiring.
Servo amplifier
NFB
L
3
L
2
L
1
MC
Power
supply
Radio noise
filter FR-BIF
-(H)
200V class: FR-BIF
400V class: FR-BIF-H
Leakage current: 4mA
29
58
42
4
Red
Blue
White
Green
44
29
7
hole
A
bo
u
t 3
0
0
5
Содержание Melservo MR-J3- 350B4
Страница 15: ...A 14 MEMO ...
Страница 21: ...6 MEMO ...
Страница 107: ...3 52 3 SIGNALS AND WIRING MEMO ...
Страница 171: ...7 16 7 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 181: ...8 10 8 TROUBLESHOOTING MEMO ...
Страница 193: ...9 12 9 OUTLINE DRAWINGS MEMO ...
Страница 295: ...12 4 12 ABSOLUTE POSITION DETECTION SYSTEM 2 For MR J3 500B or more MR J3 350B4 or more Insert connector into CN4 ...
Страница 297: ...12 6 12 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...
Страница 397: ...13 100 13 SERVO AMPLIFIERS WITH A LARGE CAPACITY 30k TO 55kW MEMO ...