5 - 19
5. PARAMETERS
No. Symbol
Name and Function
Initial
Value
Unit
Setting
Range
PC06 *COP3 Function selection C-3
Select the error excessive alarm level setting for parameter No.PC01.
0
0
Error excessive alarm level setting selection
0: 1 [rev]unit
1: 0.1 [rev]unit
2: 0.01 [rev]unit
3: 0.001[rev]unit
0
This parameter is available to software version B1 or later.
0000h Refer
to
Name
and
function
column.
PC07 ZSP Zero
speed
Used to set the output range of the zero speed (ZSP).
Zero speed signal detection has hysteresis width of 20r/min (Refer to section 3.5 (2) (b))
50 r/min 0
to
10000
PC08
For manufacturer setting
Do not change this value by any means.
0
PC09 MOD1 Analog monitor 1 output
Used to selection the signal provided to the analog monitor 1 (MO1) output. (Refer to
section 5.3.3)
C
B
5
6
7
8
9
A
D
0
1
2
3
4
Analog monitor 1 (MO1) output selection
0
Setting
Feedback position ( 10V/100 Mpulses) (Note 1, 3)
Servo motor speed ( 8V/max. speed)
Torque ( 8V/max. torque) (Note 2)
Servo motor speed (+8V/max. speed)
Torque (+8V/max. torque) (Note 2)
Current command ( 8V/max. current command)
Speed command ( 8V/max. current command)
Droop pulses ( 10V/100 pulses) (Note 1)
Droop pulses ( 10V/1000 pulses) (Note 1)
Droop pulses ( 10V/10000 pulses) (Note 1)
Droop pulses ( 10V/100000 pulses) (Note 1)
Feedback position ( 10V/1 Mpulses) (Note 1, 3)
Feedback position ( 10V/10 Mpulses) (Note 1, 3)
Bus voltage ( 8V/400V)(Note 4)
Item
0 0
Note 1. Encoder pulse unit.
2. 8V is outputted at the maximum torque.
3. It can be used by the absolute position detection system.
4. For 400V class servo amplifier, the bus voltage becomes 8V/800V.
0000h Refer
to
Name
and
function
column.
PC10 MOD2 Analog monitor 2 output
Used to selection the signal provided to the analog monitor 2 (MO2) output. (Refer to
section 5.3.3)
Select the analog monitor 2 (MO2) output
The settings are the same as those of parameter No. PC09.
0 0 0
0001h Refer
to
Name
and
function
column.
PC11 MO1 Analog monitor 1 offset
Used to set the offset voltage of the analog monitor1 (MO1) output.
0 mV
-999
to
999
Содержание Melservo MR-J3- 350B4
Страница 15: ...A 14 MEMO ...
Страница 21: ...6 MEMO ...
Страница 107: ...3 52 3 SIGNALS AND WIRING MEMO ...
Страница 171: ...7 16 7 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 181: ...8 10 8 TROUBLESHOOTING MEMO ...
Страница 193: ...9 12 9 OUTLINE DRAWINGS MEMO ...
Страница 295: ...12 4 12 ABSOLUTE POSITION DETECTION SYSTEM 2 For MR J3 500B or more MR J3 350B4 or more Insert connector into CN4 ...
Страница 297: ...12 6 12 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...
Страница 397: ...13 100 13 SERVO AMPLIFIERS WITH A LARGE CAPACITY 30k TO 55kW MEMO ...