11 - 83
11. OPTIONS AND AUXILIARY EQUIPMENT
Table 11.4 Servo motor's leakage current example (Igm)
Table 11.5 Servo amplifier's leakage current example (Iga)
Servo motor power
[kW]
Leakage current
[mA]
Servo amplifier capacity
[kW]
Leakage current
[mA]
0.05 to 1
0.1
0.1 to 0.6
0.1
2
0.2
0.75 to 3.5 (Note)
0.15
3.5 0.3
5 7 2
5 0.5
11 15 5.5
7 0.7
22 7
11 1.0
15 1.3
Note. For the 3.5kW of 400V class, leakage current is 2mA,
which is the same as for 5kW and 7kW.
22 2.3
Table 11.6 Leakage circuit breaker selection example
Servo amplifier
Rated sensitivity current of leakage
circuit breaker [mA]
MR-J3-10B to MR-J3-350B
MR-J3-10B1 to MR-J3-40B1
MR-J3-60B4 to MR-J3-350B4
15
MR-J3-500B(4) 30
MR-J3-700B(4) 50
MR-J3-11KB(4) to MR-J3-22KB(4)
100
(2) Selection example
Indicated below is an example of selecting a leakage current breaker under the following conditions:
M
NV
Ig1
Iga
Ig2
Igm
Servo
amplifier
MR-J3-40B
2mm
2
5m
2mm
2
5m
Servo motor
HF-KP43
Use a leakage current breaker generally available.
Find the terms of Equation (11.1) from the diagram:
Ig1 20
1000
5
0.1 [mA]
Ig2 20
1000
5
0.1 [mA]
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (11.1):
Ig 10 {0.1 0 0.1 1 (0.1 0.1)}
4.0 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity current (Ig)
of 4.0[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-SP/SW/CP/CW/HW
series.
Содержание Melservo MR-J3- 350B4
Страница 15: ...A 14 MEMO ...
Страница 21: ...6 MEMO ...
Страница 107: ...3 52 3 SIGNALS AND WIRING MEMO ...
Страница 171: ...7 16 7 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 181: ...8 10 8 TROUBLESHOOTING MEMO ...
Страница 193: ...9 12 9 OUTLINE DRAWINGS MEMO ...
Страница 295: ...12 4 12 ABSOLUTE POSITION DETECTION SYSTEM 2 For MR J3 500B or more MR J3 350B4 or more Insert connector into CN4 ...
Страница 297: ...12 6 12 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...
Страница 397: ...13 100 13 SERVO AMPLIFIERS WITH A LARGE CAPACITY 30k TO 55kW MEMO ...