3 - 16
3. SIGNALS AND WIRING
(b) Termination of the cables
1) CNP1 CNP3
Solid wire: After the sheath has been stripped, the cable can be used as it is.
7mm
Sheath
Core
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take care to avoid a
short caused by the loose wires of the core and the adjacent pole. Do not solder the core as it
may cause a contact fault. Alternatively, a bar terminal may be used to put the wires together.
Cable size
Bar terminal type
[mm
2
] AWG
For 1 cable
For 2 cables
Crimping tool
Manufacturer
1.25/1.5 16 AI1.5-8BK
AI-TWIN2 1.5-8BK
2.0/2.5 14 AI2.5-8BU
AI-TWIN2 2.5-10BU
CRIMPFOX-ZA3
Phoenix Contact
3.5 12
AI4-10GY
2) CNP2
CNP2 is the same as MR-J3-100B or smaller capacities. Refer to (1) (b) of this section.
(3) MR-J3-60B4 to MR-J3-200B4
(a) Servo amplifier power supply connectors
<Applicable cable example>
Cable finish OD: 4.1mm or less
Servo amplifier
Connector for CNP3
721-203/026-000(Plug)
(WAGO JAPAN)
Servo amplifier power supply connectors
CNP2
CNP1
CNP3
Connector for CNP1
721-207/026-000(Plug)
(WAGO JAPAN)
Connector for CNP2
721-205/026-000(Plug)
(WAGO JAPAN)
Содержание Melservo MR-J3- 350B4
Страница 15: ...A 14 MEMO ...
Страница 21: ...6 MEMO ...
Страница 107: ...3 52 3 SIGNALS AND WIRING MEMO ...
Страница 171: ...7 16 7 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 181: ...8 10 8 TROUBLESHOOTING MEMO ...
Страница 193: ...9 12 9 OUTLINE DRAWINGS MEMO ...
Страница 295: ...12 4 12 ABSOLUTE POSITION DETECTION SYSTEM 2 For MR J3 500B or more MR J3 350B4 or more Insert connector into CN4 ...
Страница 297: ...12 6 12 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...
Страница 397: ...13 100 13 SERVO AMPLIFIERS WITH A LARGE CAPACITY 30k TO 55kW MEMO ...