3 - 50
3. SIGNALS AND WIRING
3.12 Grounding
WARNING
Ground the servo amplifier and servo motor securely.
To prevent an electric shock, always connect the protective earth (PE) terminal
(terminal marked ) of the servo amplifier with the protective earth (PE) of the
control box.
The servo amplifier switches the power transistor on-off to supply power to the servo motor. Depending on the
wiring and ground cable routing, the servo amplifier may be affected by the switching noise (due to di/dt and
dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always ground.
To conform to the EMC Directive, refer to the EMC Installation Guidelines (IB(NA)67310).
L
1
L
2
L
3
L
11
L
21
CN1A
NFB
MC
CN2
U
V
W
M
U
V
W
Control box
Servo amplifier
Li
ne
filt
er
Protective earth(PE)
Outer
box
Servo motor
Encoder
(Note)
Power supply
Se
rv
o s
yste
m
co
nt
ro
ller
Ensure to connect it to PE
terminal of the servo amplifier.
Do not connect it directly
to the protective earth of
the control panel.
Note: For 1-phase 200V to 230VAC, connect the power supply to L
1
L
2
and leave L
3
open.
There is no L
3
for 1-phase 100 to 120VAC power supply. Refer to section 1.3 for the power supply specification.
Содержание Melservo MR-J3- 350B4
Страница 15: ...A 14 MEMO ...
Страница 21: ...6 MEMO ...
Страница 107: ...3 52 3 SIGNALS AND WIRING MEMO ...
Страница 171: ...7 16 7 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 181: ...8 10 8 TROUBLESHOOTING MEMO ...
Страница 193: ...9 12 9 OUTLINE DRAWINGS MEMO ...
Страница 295: ...12 4 12 ABSOLUTE POSITION DETECTION SYSTEM 2 For MR J3 500B or more MR J3 350B4 or more Insert connector into CN4 ...
Страница 297: ...12 6 12 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...
Страница 397: ...13 100 13 SERVO AMPLIFIERS WITH A LARGE CAPACITY 30k TO 55kW MEMO ...