13. SERVO AMPLIFIERS WITH A LARGE CAPACITY (30k TO 55kW)
(2) Remedies for alarms
CAUTION
When any alarm has occurred, eliminate its cause, ensure safety, then reset the
alarm, and restart operation. Otherwise, injury may occur.
POINT
When any of the following alarms has occurred, always remove its cause and
allow about 30 minutes for cooling before resuming operation. If operation is
resumed by switching control circuit power off, then on to reset the alarm, the
converter unit and regenerative option may become faulty.
Regenerative error (A.30)
Over load 1 (A.50)
Over load 2 (A.51)
Main circuit device overheat (A.45)
The alarm can be deactivated by switching the power off, then on or by the
error reset command from the host controller. Refer to (1) in this section for
details.
When an alarm occurs, the trouble (ALM) signal switches off and the display section shows the alarm number.
Remove the cause of the alarm in accordance with this section.
Display Name
Definition
Cause
Action
1. Instantaneous control power failure
occurred for more than 60ms.
2. Shortage of power supply capacity
caused the power supply voltage to
drop at start, etc.
Review the power supply.
A.10 Undervoltage Power
supply
voltage
dropped.
3. Failure of the part in the converter
unit.
Checking method
Alarm (A.10) occurs if power is
switched on after connectors
disconnected.
Change the Converter unit.
A.12 Memory
error1
(RAM)
RAM memory fault
Failure of the part in the converter unit.
Checking method
Alarm (A.12) occurs if power is
switched on after connectors
disconnected.
Change the converter unit.
1. Failure of the part in the converter
unit.
Checking method
Alarm (A.15) occurs if power is
switched on after connectors
disconnected.
A.15 Memory
error2
(EEP-ROM)
EEP-ROM fault
2. The number of write times to EEP-
ROM exceeded 100,000.
Change the converter unit.
A.17
Board error
CPU/parts fault
Failure of the part in the converter unit.
A.19 Memory
error3
(Flash-ROM)
ROM memory fault
Checking method
Alarm (A.17/A.19) occurs if power is
switched on after connectors
disconnected.
Change the converter unit.
Содержание Melservo MR-J3- 350B4
Страница 15: ...A 14 MEMO ...
Страница 21: ...6 MEMO ...
Страница 107: ...3 52 3 SIGNALS AND WIRING MEMO ...
Страница 171: ...7 16 7 SPECIAL ADJUSTMENT FUNCTIONS MEMO ...
Страница 181: ...8 10 8 TROUBLESHOOTING MEMO ...
Страница 193: ...9 12 9 OUTLINE DRAWINGS MEMO ...
Страница 295: ...12 4 12 ABSOLUTE POSITION DETECTION SYSTEM 2 For MR J3 500B or more MR J3 350B4 or more Insert connector into CN4 ...
Страница 297: ...12 6 12 ABSOLUTE POSITION DETECTION SYSTEM MEMO ...
Страница 397: ...13 100 13 SERVO AMPLIFIERS WITH A LARGE CAPACITY 30k TO 55kW MEMO ...