e) Read the resultsTable
–
dataStore.queryResultsTable.queryResultsEntry.rowMeasureT
ime.x
will provide the UTC timestamp of the measure values reported by the
corresponding
dataStore.queryResultsTable.queryResultsEntry.rowValues.x
OID.
f) Clear the result set (and query parameters) by writing a value of 7 (done) to
the
dataStore.queryCommandAndStatus.0
OID.
rowValues is an OctetString
– containing one 32bit (signed or unsigned, depending
on the corresponding sensor OID entry) integer value for each OID reported in the
historySensorOidTable
– in exactly the same sequence as the sensor OIDs in above
table.
If data for a longer time period, or with a different reporting interval (greater than the
store interval of 1 minute) should be reported, the following sequence of SNMP
requests can be used:
a) Read the historySensorTable (i.e. read the number of entries in the
historySensorTable via
dataStore.numHistorySensorEntries.0
, and
then read the entries). The sequence of these OIDs will be used in the
resultsTable to report the respective oid values.
b) Write the desired value for the reporting interval (if data should be reported in
an interval > 1 minute) to the
dataStore.reportingInterval.0
OID.
Valid values are:
1, 2, 3, 4, 5, 6, 8, 10, 12, 15, 20, 30 or 60 minutes.
c) Write the desired start timestamp to the
dataStore.queryStartTime.0
OID. The rpu stores data up to 1 year
– so the timestamp might not be more
than one year in the past!
d)
Write a value of “2” (runQuery) to the
dataStore.queryCommandAndStatus.0
OID
e) Read the
dataStore.queryCommandAndStatus.0
OID until the status
changes from 2 (runQuery) to another value. The resulting value indicates
weather the query was successful or not. A value of 3 (dataReady) or 4
(dataPartialReady) indicates the query was successful, and the result is
provided in the queryResultsTable
Содержание 8511.EAK
Страница 1: ...Operating Manual LCom Lufft Communicator Order No 8511 EAK Version V2 18 1 11 2019 www lufft com ...
Страница 41: ...5 8 2 8 essSubSurfaceSensorTable The parameters for the subsurface temperature sensors are configured here ...
Страница 42: ...5 8 2 9 essSnapShotCameraTable The camera s is are configured here See Camera Support below ...
Страница 124: ...Manual LCom Page 124 of 158 The button show events opens a dialog showing the events stored on the device ...
Страница 133: ...Manual LCom Page 133 of 158 reactivated by disconnecting and reconnecting the USB stick wait time 3 seconds ...
Страница 153: ...Manual LCom Page 153 of 158 6 2 Connection Example ...